Plan Review Details - Permit 16110574
Plan Review Stops For Permit 16110574
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By jwitmer Date 2017-02-09 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2017-02-09 Time 09:01 Sent To  
Notes
2017-02-09 09:41:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110574
 ADD: 3200 N. CONGRESS
 CONT: HEDRICK BROTHERS
 TEL: 561-308-2954
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. FEB. 09/2017
 ACTION: DENIED
  
 1) BUILDING PROVISO: DEFERRED SUBMITTALS 107.3.4.2
 REQUEST.
 1.1) EXTERIOR WINDOWS AND DOORS
 1.2) WOOD TRUSSES
 1.3) ALUMINUM LOUVER PANELS
 1.4) ROOFING ASSEMBLIES
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2016-12-06 Time 06:30 Sent To  
Notes
2016-12-06 07:38:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110574
 ADD: 3200 N. CONGRESS
 CONT: HEDRICK BROTHERS
 TEL: 561-308-2954
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 06/2016
 ACTION: DENIED
  
 1) SHEET 002_A001 THE SITE PLAN UNDER THE HEADING OF
 BUILDING DATA LIST THIS BUILDING OCCUPANCY AS A UTILITY
 CLASSIFICATION.
 SECTION 312 OF THE 2014 FBC-B LIST SHEDS, CARPORTS,
 PRIVATE GARQAGES AND BARNS AS EXAMPLES OF A UTILITY
 OCCUPANCY, NONE OF THESE TYPE STRUCTURES HAVE
 OCCUPIABLE SPACE. THIS SPACE RESEMBLES MORE A BUSINESS
 TYPE OF OCCUPANCY WHERE ONE OR MORE PERSONS MONITORS
 THE SECURITY OF THE DEVELOPMENT BY WHO ENTERS THE
 PROJECT. PLEASE ALSO NOTE UNDER TABLE 1004.1.2. THERE
 ARE NO CLASSIFICATIONS FOR OCCUPANT LOADS FOR THE
 UTILITY USAGE. WITH A BUSINESS OCCUPANCY A OCCUPANCY
 LOAD OF 3 WOULD BE ASSIGNED TO THE BUILDING.
  
 2) SHEET 006_A102 THE KITCHENETTE DETAIL SHOWS A
 MICROWAVE ABOVE THE REACH RANGES AND RANGE FOR OPERABLE
 PARTS. SEE THE 2014 FBC-ACCESSIBILITY CODE SECTIONS 308
 & 309 FOR CODE COMPLIANCE.
  
 3) SHEET 014-A501 THE WATER CLOSET GRAB BARS THE
 HEIGHTS ARE LISTED FROM FINISH FLOOR TO THE CENTERLINE
 OF THE GRAB BARS. PLEASE REVIEW THE 2014
 FBC-ACCESSIBILITY CODE. THIS CODE MEASURES THE GRAB BAR
 TO THE TOP OF THE GRASABLE SURFACE SEE SECTION 609.4.
  
 4) SHEET 016_A602 DETAIL FOR SLIDING DOOR HEAD DETAIL
 INDICATES THE USE OF BLOCKING/ BUCK. THE NOTE INDICATES
 FASTENERING PER MANUFACTURERS RECOMMENDATIONS. PLEASE
 NOTE PRODUCT APPROVALS DO NOT INDICATE HOW TO FASTEN
 BUCKS, THAT IS UP TO THE DESIGN PROFESSIONAL TO PROVIDE
 THE THICKNESS OF THE BUCKS AND ANCHORS. PLEASE ALSO SEE
 THE REQUIREMENTS IN THE 2014 FBC-B 1710.10 MASONRY,
 CONCRETE OR OTHER STRUCTURAL SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1
 1/2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
  
 WHERE THE WOOD BUCK THICKNESS IS 1 1/2 INCHES (38 MM)
 OR GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 5) NOTED: BUILDING PROVISO: DEFERRED SUBMITTALS
 107.3.4.2 REQUEST.
 5.1) EXTERIOR WINDOWS AND DOORS
 5.2) WOOD TRUSSES
 5.3) ALUMINUM LOUVER PANELS
 5.4) ROOFING ASSEMBLIES
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-06 Cont ID  
Sent By vperez Date 2017-02-06 Time 16:09 Rev Time 0.00
Received By vperez Date 2017-02-06 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-12 Cont ID  
Sent By vperez Date 2016-12-12 Time 08:15 Rev Time 0.00
Received By vperez Date 2016-12-12 Time 08:15 Sent To  
Notes
2016-12-12 08:23:18INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR GENERATOR,
 ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO
 FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA,
 SIGNAGE, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE
 REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM
 COVER REQUIREMENTS FOR CONDUITS AND THE PLACEMENT OF A
 WARNING RIBBON FOR THE SERVICE LATERAL CONDUCTORS SHOWN
 FOR THIS PROJECT. A NOTE WILL SUFFICE
 3. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT
 ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY
 REGULATORY AGENCIES.
 4. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR
 FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7
 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 6. PROVIDE AIC CALCULATION FOR THE NEW SERVICE SHOWN.
 FBC 107.3.5
 7. LABEL GFCI PROTECTED ALL EXTERIOR RECEPTACLES. NEC
 210.8B(4)
 8. LABEL INTERIOR RECEPTACLES WITHIN 6FT OF THE SINKS
 TO BE GFCI PROTECTED. NEC 210.8B(5)
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2017-02-24 Cont ID  
Sent By skennedy Date 2017-02-24 Time 16:51 Rev Time 0.00
Received By skennedy Date 2017-02-24 Time 16:51 Sent To  
Notes
2017-02-24 16:52:31PER MGONZALEZ EMAIL OF 2/24/17, ENGINEERING REVIEW WILL
 OCURR WITH THE FORMAL CIVIL SUBMITTAL ONLY.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2017-01-13 Cont ID  
Sent By lmarchan Date 2017-01-13 Time 10:48 Rev Time 0.00
Received By lmarchan Date 2017-01-13 Time 10:48 Sent To  
Notes
2017-01-13 10:48:18REVIEW TO BE DONE DURING 2ND REVIEW CYCLE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-02-10 Cont ID  
Sent By pleduc Date 2017-02-10 Time   Rev Time 0.00
Received By pleduc Date 2017-02-10 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-23 Cont ID  
Sent By pleduc Date 2016-11-23 Time   Rev Time 0.00
Received By pleduc Date 2016-11-23 Time 14:03 Sent To  
Notes
2016-11-23 15:13:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) BOTH GATES SHALL OPEN FOR EMERGENCY VEHICLE
 ACCESS/EGRESS.
  
  
  
 2) PROVIDE KNOX KEY SWITCH FOR OPENING GATES IF IT IS
 NOT A 24HR SECURITY ATTENDANT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-15 Cont ID  
Sent By jwitmer Date 2017-08-15 Time 15:16 Rev Time 0.00
Received By jwitmer Date 2017-08-14 Time 17:23 Sent To  
Notes
2017-08-15 15:16:20AUGUST 15/ 2017
 PALM BEACH COUNTY IMPACT FEES
 RECEIPT NUMBER 2017-0628-231
 TRACKING NUMBER: MU-2017-015578-0000
 FEES: $1,941.52
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
2017-08-14 17:23:17IMPACT FEES GIVEN TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-14 Cont ID  
Sent By cpuell Date 2017-04-14 Time 15:42 Rev Time 0.00
Received By cpuell Date 2017-03-15 Time 12:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-27 Cont ID  
Sent By lmarchan Date 2017-02-27 Time 14:35 Rev Time 0.00
Received By lmarchan Date 2017-01-26 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-13 Cont ID  
Sent By lmarchan Date 2017-01-13 Time 10:48 Rev Time 0.00
Received By lmarchan Date 2016-11-17 Time 08:53 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2017-08-15 Cont ID  
Sent By jwitmer Date 2017-08-15 Time 15:18 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-08-15 15:19:36AUGUST 15/ 2017
 PALM BEACH COUNTY IMPACT FEES
 RECEIPT NUMBER 2017-0628-231
 TRACKING NUMBER: MU-2017-015578-0000
 FEES: $1,941.52
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-02-09 Cont ID  
Sent By jwitmer Date 2017-02-09 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2017-02-09 Time 09:42 Sent To  
Notes
2017-02-09 09:42:33IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 07:39 Rev Time 0.00
Received By jwitmer Date 2016-12-06 Time 07:39 Sent To  
Notes
2016-12-06 07:39:25 
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-03-24 Cont ID  
Sent By ccole Date 2017-03-24 Time 16:26 Rev Time 0.00
Received By ccole Date 2017-03-24 Time 16:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-06 Cont ID  
Sent By ccole Date 2017-02-06 Time 10:48 Rev Time 0.00
Received By ccole Date 2017-02-06 Time 10:48 Sent To  
Notes
2017-02-06 10:55:202ND REVIEW FBC-2014 MECHANICAL
 PERMIT #167110574
 2/6/17
  
 1) MECHANICAL VENTILATION CALCULATIONS ARE SHOWN ON
 SHEET M1.1, HOWEVER PER THE NARRATIVE RESPONSE, NO
 MECHANICAL VENTILATION IS BEING PROVIDED. PLEASE
 PROVIDE THE NATURAL VENTILATION CALCULATION ON THE PLAN
 AS INDICATED IN THE NARRATIVE
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-02 Cont ID  
Sent By ccole Date 2016-12-02 Time 17:01 Rev Time 0.00
Received By ccole Date 2016-12-02 Time 17:01 Sent To  
Notes
2016-12-02 17:08:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110574
 12/2/16
  
 1) PROVIDE A VENTILATION CALCULATION FOR THE NEW GUARD
 HOUSE IN COMPLIANCE WITH TABLE 403.3, AND SHOW HOW
 OUTDOOR AIR WILL BE PROVIDED TO THE SPACE- SEESECTION
 401.2.
  
 2) THE AC SCHEDULE DOES NOT SHOW ANY DATA FOR HEATING.
 IS THIS UNIT A HEAT PUMP? PLEASE REFER TO SECTION 309.1
 AND SHOW COMPLIANCE.
  
 3) THE ENGINEER OF RECORD MUST PROVIDE HIS SIGNATURE
 AND SEAL TO THE SUMMARY AC CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-27 Cont ID  
Sent By gjohnson Date 2017-02-27 Time 11:34 Rev Time 0.00
Received By gjohnson Date 2017-02-27 Time 11:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-20 Cont ID  
Sent By gjohnson Date 2016-12-20 Time 15:53 Rev Time 0.00
Received By gjohnson Date 2016-12-20 Time 14:47 Sent To  
Notes
2016-12-20 16:16:391ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER FBC ACC 604.9.6
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE!!TOP
 OF THE GRIPPING SURFACE!!, PER FBC ACC 609.4
  
 3. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4. TEMPERED WATER REQUIRED AT LAVATOR PERFBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 5. PLEASE PROVIDE A SITE PLAN SHOWING THE SAN SEWER,
 WATER AND STORM PIPING METERS AND BACK FLOW PER WPB
 AMEND TO FBC 107.2.1
  
 6. SEPARATE PERMIT REQUIRED FOR BACK FLOW. PER WPB
 UTILITIES

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2017-10-24 Cont ID  
Sent By cpuell Date 2017-10-24 Time 15:11 Rev Time 0.00
Received By cpuell Date 2017-10-24 Time 15:11 Sent To  
Notes
2017-03-24 16:27:50MECH DIG-SIGS VERIFIED ON PLANS AND DOCS
 CCOLE/3/24/17
2017-02-27 11:36:102/27/27 SIG ON PLUMB PG OK GPJ
2016-12-05 09:47:3112/02/16 HARD COPIES OF PLANS LOCATED IN LIBRARY. LEM
2016-11-16 14:03:4811/16/16 - CIVIL DRAWINGS WILL BE FOR REFERENCE ONLY -
 DOES NOT NEED DIGITAL SIGNATURE. LEM

Review Stop Z ZONING
Rev No 4 Status P Date 2017-10-24 Cont ID  
Sent By jroach Date 2017-10-24 Time 14:43 Rev Time 0.00
Received By jroach Date 2017-10-24 Time 14:43 Sent To  
Notes
2017-10-24 14:46:541. THIS PERMIT IS APPROVED FOR THE STRUCTURE ONLY.
  
 2. SEPARATE PERMIT(S) REQUIRED FOR LANDSCAPING AND
 IRRIGATION.
  
 3. SITE WORK SHALL BE COVERED UNDER SEPARATE CIVIL
 PERMIT(S). PLEASE NOTE THAT THE PARKING SPACE/REJECTION
 LANE SHOWN ON THIS PARTIAL SITE PLAN DOES NOT CONFORM
 TO THE MINIMUM REQUIREMENTS - A MINIMUM OF 24 FEET
 SHALL BE PROVIDED BEHIND THE PARKING SPACE TO ALLOW FOR
 BACK OUT.

Review Stop Z ZONING
Rev No 3 Status F Date 2017-04-14 Cont ID  
Sent By jroach Date 2017-04-14 Time 14:43 Rev Time 0.00
Received By jroach Date 2017-04-14 Time 14:43 Sent To  
Notes
2017-04-14 14:43:48ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.14.2017
 PERMIT NO.: 16110574
 ADDRESS: 3200 CONGRESS AVENUE
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW GUARDHOUSE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A FORMAL
 SITE PLAN REVIEW APPLICATION SHALL BE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION.
 THIS APPLICATION HAS BEEN SUBMITTED AND COMMENTS WERE
 ISSUED BY THE PLANS AND PLATS REVIEW COMMITTEE
 (INCLUDING ZONING COMMENTS). ALL COMMENTS SHALL BE
 ADDRESSED AND AN APPROVAL LETTER ISSUED PRIOR TO
 ISSUANCE OF A BUILDING PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-02-27 Cont ID  
Sent By jroach Date 2017-02-27 Time 14:03 Rev Time 0.00
Received By jroach Date 2017-02-27 Time 14:03 Sent To  
Notes
2017-02-27 14:24:04ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.27.2017
 PERMIT NO.: 16110574
 ADDRESS: 3200 CONGRESS AVENUE
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW GUARDHOUSE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A FORMAL
 SITE PLAN REVIEW APPLICATION SHALL BE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION.
 THIS APPLICATION HAS BEEN SUBMITTED AND COMMENTS WERE
 ISSUED BY THE PLANS AND PLATS REVIEW COMMITTEE
 (INCLUDING ZONING COMMENTS). ALL COMMENTS SHALL BE
 ADDRESSED AND AN APPROVAL LETTER ISSUED PRIOR TO
 ISSUANCE OF A BUILDING PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By jroach Date 2016-12-28 Time 15:34 Rev Time 0.00
Received By jroach Date 2016-12-28 Time 15:34 Sent To  
Notes
2016-12-28 15:34:59ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.28.2016
 PERMIT NO.: 16110574
 ADDRESS: 3200 CONGRESS AVENUE
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW GUARDHOUSE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A FORMAL
 SITE PLAN REVIEW APPLICATION SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION. THE SITE PLAN REVIEW APPLICATION
 SHALL INCLUDE A FINAL SITE PLAN AND LANDSCAPE PLANS FOR
 THE ENTIRE ENTRANCEWAY. ALL ZONING COMMENTS WILL BE
 MADE DURING THE SITE PLAN REVIEW PROCESS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved